TUV EN50618 H1Z2Z2-K & IEC62930 Solar cable 1* X mm2 & 2*X mm2 | ||
Conductor | Tinned fine Re copper strands,according to IEC60228.Class5 | |
Insulation | LSZH electron-beam cross-linked Polyolefin copolymer ROHS material, prior color black or as per customer's request | |
Sheath Jacket | LSZH & UV-resistant electron-beam cross-linked Polyolefin copolymer ROHS material, prior color black or as per customer's request. | |
Sheath color | Red/Black | |
Nominal Voltage | UO/U 1.0/1.0 KV (AC) , 1.5/1.5kV (DC) | |
Test voltage | No breakdown at 6.5 kV (AC) 50HZ 5min 20±5°C /15kV(DC) 5min 20±5°C | |
Temperature Rating | Working Temperature —40C 〜+ 90 °C, Max conductor Temperature 125 °C (continuously 20h), Allowable short circuit temperature 200°C in 5 second | |
Fire-resistant Performance | IEC 60332-1:2004 | |
Smoke Emission | IEC61034-1, min 60% luminousness;EN50268-2 | |
Halogen Conten | EN 50525-1:2011, Appendix B | |
Low Fire Load | DIN 51900 | |
Executive Standard | EN 50618:2014 | |
Certification | TUV EN50618 H1Z2Z2-K & IEC62930 |
Construction (Nxmm2) | Finished Cable OD(mm) | Max DC Resistance at 20 C (Q/KM) | Current (A) |
Underground installation | |||
1x2.5 mm2 | 5.05±0.2 | 8.21 | 39 |
1x4 mm2 | 5.55±0.3 | 5.09 | 52 |
1x6 mm2 | 6.15±0.3 | 3.39 | 67 |
1x10 mm2 | 7.4±0.3 | 1.95 | 93 |
1x16 mm2 | 8.72±0.3 | 1.25 | 125 |
2x2.5 mm2 | 5.55±0.3×11.6±0.5 | 8.21 | 39 |
2x4 mm2 | 5.05±0.3×10.5±0.5 | 5.09 | 52 |
2x6 mm2 | 6.15±0.3×12.9±0.6 | 3.39 | 67 |
2x10 mm2 | 7.4±0.3×15.4±0.8 | 1.95 | 93 |
2x16 mm2 | 8.72±0.3×18.1±0.8 | 1.25 | 125 |